Home - Product center - Digital Panel Meter - Digital Intelligent Multi functional Electric Meter

HP192E-□TY+Series Harmonic Analysis Multi-functional Electric Meter

HP192E-□TY+Series Harmonic Analysis Multi-functional Electric Meter

HP192E-□TY+Series Harmonic Analysis Multi-functional Electric Meter

Product Profile
功能特点HP192E-□TY+series harmonic analysis multi-functional power meter is an upgrading and enhanced version of HP192E series multi-functional meter. It can real-time measure and display the electric parameters of electric circuits such as thr

功能特点

HP192E-□TY+series harmonic analysis multi-functional power meter is an upgrading and enhanced version of HP192E series multi-functional meter. It can real-time measure and display the electric parameters of electric circuits such as three-phase current, three-phase voltage, frequency, power, power factor, four-quadrant electrical energy and so on, at the same time, it can provide the analysis information such as the total harmonic content of three-phase voltage and three-phase current, the odd harmonic content, the even harmonic content, the 2~21 times subharmonic content and so on. It is applicable in the electric power circuit to real-time collect and analyze the quality of electric energy, so as to realize the analysis and remote management of quality of electric energy. It has the following features:
★True RMS measurement, frequency and waveform change will not influence the accuracy of measurement.
FSTN industrial grade wide angle of view LCD display.
Variable ratio can be set, it can also expand the functions of switching value input, switching value output, analog value output and communication.
Switching value output is remote control signal, and it's also the upper and lower limit out-of-limit alarming contact signal.
Analog quantity can be set freely:0~10mA,0~20mA,4~20mA.
Standard RS-485 communication interface, MODBUS-RTU communication agreement, baud rate 1200~19200.
It has the functions of harmonic analysis, unbalance degree analysis, extreme value statistics, and so on.
Efficient installation method, firm and reliable.

Measuring Parameter

Phase-zero voltage,phase-phase voltage 
Each phase current 
Total active power,each phase active power 
Total reactive power,each phase reactive powerTotal apparent power,each phase apparent power 
Total power factor,each phase power factor 
Frequency 
Positive active energy,reverse active energy 
Positive reactive energy,reverse reactive energy 
Four-quadrant status indication 
Maximum value of each phase voltage and each phase current(only provide the communication data)
Minimum value of each phase voltage and each phase current(only provide the communication data)

Maximum demand value of active power 
Present maximum demand value of active power(only provide the communication data)
Unbalance degree of three-phase voltage (only provide the communication data)Unbalance degree of three-phase current (only provide the communication data)
Total harmonic distortion rate of each phase current(THD)
2-31times subharmonic distortion rate of each phase current(only provide the communication data)
Total harmonic distortion rate of each phase voltage(THD)
2~31 times subharmonic distortion rate of each phase voltage (only provide the communication data)
Total harmonic factor of each phase voltage(THF )(only provide the communication data)
Total harmonic factor of each phase current(THF)(only provide the communication data)
Crest factor of each phase voltage(only provide the communication data)
Total K factor of each phase voltage(only provide the communication data)
Sequence value of each phase voltage(positive sequence,negative sequence,zero sequence )(only provide the communication data)
Switching value input and switching value output status 
Communication status indication

Model & Specification & Selection Table

Basic Parameter

★Inputspecification:3xAC220V/380V5A,3xAC57.5V/100V 5A 
Frequency range:40~65Hz 
Power consumption of input loop:<1VA/phase 
Overload capacity: last 1.2 times 
Resolving ability: for voltage, maximum is 0.1V; for current, maximum is 0.001A; decimal point will shit automatically
Measuring accuracy: for voltage, current and power, is t(0.5% FS); for frequency, is±0.1Hz; for power factor, ist0.01 PF; for active energy, is class 1.0; for reactive energy, is class 2.0
Measuring rate: about 1 time/s 
Auxiliary power supply: AC/DC 80~260V(power consumption <5VA)
RS485 communication:1-channel, baud rate can be set from 1200~9600, data format is n8.2
Communication protocol: MODBUS-RTU 
Analog output: it defaults as DC 4~20mA, load<500Ω

Terminal Layout and Connection

Same as HP192E-□TY series meter.