Function Feature
It adopts the three-row four-digit LED display and status indicator to real-time measure and display the voltage, current, frequency, power, four-quadrant electrical energy and so on electric parameters of three-phase electric circuits. It also adopt simplified design scheme, with high cost performance.
★Short shell design, compact, economical and practical.
★True RMS measurement, frequency and waveform change will not influence the accuracy of measurement.
★It can display directly multiple electric parameters at the same time.
★Variable ratio can be set.
★It can extend one channel RS485 communication interface, MODBUS-RTU communication protocol.
★Buckle mounting way makes the installation efficient, firm and reliable.
Measuring and Display
★Phase-zero voltage(VL_N)
★Phase-phase votlage(VL_L)
★Each phase current(A)
★Frequency(Hz)
★Three-phase total active power(∑W)
★Three-phase total reactive power(∑var)
★Three-phase total power factor(∑COSφ)
★Positive active energy(+Wh)
★Reverse active energy(-Wh)
★Positive reactive energy(+varh)
★Reverse reactive energy(-varh)
★Each phase active power
(only provide the communication data)
★Each phase reactive power
(only provide the communication data)
★Each phase apparent power
(only provide the communication data)
★Total apparent power(∑VA)
(only provide the communication data)
★Each phase power factor(COSφ)
Basic Parameter
★Input specification:3xAC 220V/380V5A,3xAC 57.5V/100V 5A
★Frequency range:40~65Hz
★Power consumption of input loop:<1VA/phase
★Overload capacity: last 1.2 times
★Resolving ability: for voltage, maximum is 0.1V; for current, maximum is 0.001A; decimal point will shift automatically
★Measuring accuracy: for voltage, current and power, is t(0.5% FS) for frequency, is ± 0.1Hz; for power factor, is ±0.01 PF for active energy, is class 1.0; for reactive energy, is class 2.0
★Measuring rate: about 1 time/s
★Aux. power supply: AC220V/380V(can be customized AC/DC 90~270V)
★Power consumption of power supply:<3VA
★Working environment: temperature is-10~+50℃, humidity <85% RH, without any corrosive gas
★Safety withstand voltage: the testing between the measuring input terminal and power supply terminal can pass the AC2kV withstand voltage test
★RS485 communication: defaulted as no, it can be extended as one channel and adopts the MODBUS-RTU protocal
Contour and Installation Size(unit:mm)
Typical Connection